Available Models:
Features:
Ideal as a tower monitor on center pivot
irrigation systems
Adjustable trip level
Adjustable trip delay
Approvals:
CP-5-115
CP-5-460
Specications
The Model CP-5
is an undercurrent monitor designed to monitor
one leg of a 3-phase system. It is commonly used as
a tower monitor on center pivot irrigation systems
to detect stalled or jammed towers to prevent
overwatering.
The CP-5 has both an adjustable trip level and an
adjustable trip delay timer. When the current is
sensed, the Model CP-5 activates its output relay,
thus starting the motor/pump. When the current
in the monitored power line falls below the user-
selectable trip point, the unit goes through a trip
delay timer and then deactivates the output relay if
the monitored current does not recover first.
For more information see:
See Appendix A, page 68, Figure 7 for dimensional
drawing.
See Appendix B, page 81, Figure 52 for typical
wiring diagrams.
Model CP-5
single-phase current monitor, adjustable trip delay, adjustable trip level, trips on undercurrent
Single-Phase Current Monitor
Input Characteristics
Nominal Input Voltage
CP-5-115 .......................................115VAC
CP-5-460 .......................................460VAC
Frequency .....................................50*/60Hz
Functional Characteristics
Operating Points
Trip Level .....................................0-5 Amps
Trip Delay .....................................0-10 minutes
Restart ........................................1 second
Output Characteristics
Output Contact Rating (SPDT)
Pilot Duty
CP-5-115 .......................................480VA @ 240VAC
CP5-460 .........................................470VA @ 600VAC
General Characteristics
Terminal
Torque ........................................7 in.-lbs.
Wire Size ......................................12-18AWG
Safety Marks
UL ............................................UL508 (File #E68520)
Dimensions ....................................2.93”H x 5.27”W x 2.95”D
(74.4 x 133.9 x 74.9mm)
Weight ........................................1 lb. (16 oz., 453.59 g)
Mounting Method ..............................#8 screws
*Note: 50Hz will increase all delay timers by 20%