www.symcom.com • 800-843-8848 • fax: 605-348-5685
35
Available Models:
Features:
Protects from high and low voltage (low
voltage only for 202-200-SP-NHV
Protects against rapid cycling
Quick mounting with single screw
Adjustable restart delay setting
Small package, ideal for assembly into
panels
Standard 1/4” quick connects
A
pprovals:
202-200-SP
202-200-SP-NHV
Specications
The Model 202-200-SP
voltage monitor is designed to protect single-
phase motors regardless of size. It can be used
with 190V-240VAC, 50/60Hz motors to prevent
damage caused by incoming power problems.
A unique microcontroller-based voltage-sensing
circuit constantly monitors the voltage to detect
harmful power line conditions. When a harmful
condition is detected, the MotorSaver’s output
relay is deactivated after a specified trip delay. The
output relay reactivates after power line conditions
return to an acceptable level and a specified
amount of time has elapsed (restart delay). The trip
delay prevents nuisance tripping due to rapidly
fluctuating power line conditions.
For more information see:
See Appendix A, page 68, Figure 9 for dimensional
drawing.
See Appendix B, page 77, Figures 31 & 32 for typical
wiring diagrams.
Model 202-200-SP
single-phase voltage monitor, panel mount, adjustable or manual restart delay
Single-Phase Voltage Monitor
General Characteristics
Temperature Range ...................................-40° to 70°C (-40° to 158°F)
Trip & Reset Accuracy ................................±1%
Repeatability .........................................±0.5%
Input to Output Dielectric .............................1480 Vrms (min.)
Termination ..........................................0.25” male quick connect
Maximum Input Power ...............................5 W
Relative Humidity ....................................95%, non-condensing
Transient Protection ..................................IEC 61000-4-5, ±4kV
Safety Marks
UL, UL Recognized ..................................... UL508
(File #E68520)
Dimensions .........................................2.5” H x 2.5” W x 1.4” D
(63.5 x 63.5 x 35.56mm)
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.5 lb. (8 oz., 226.8 g)
Mounting Method ....................................1/4” socket head cap screw
(customer supplied)
*Note: 50Hz will increase all delay timers by 20%.
Input Characteristics
Line Voltage
202-200-SP, 202-200-SP-NHV ...........................190-240VAC
Frequency ...........................................50*/60Hz
Functional Characteristics
Low Voltage (% of setpoint)
Trip .................................................90%
Reset ................................................93%
High Voltage (% of setpoint) (Not available on -NHV model)
Trip .................................................110%
Reset ................................................107%
Trip Delay Time
High and Low Voltage ................................4 seconds
Restart Delay Time
After a fault or
complete power loss ..................................Manual, 2-300 seconds adj.
Output Characteristics
Output Contact Rating (SPDT)
Pilot Duty ...........................................480VA @ 240VAC
General Purpose ......................................10A @ 240
VAC