www.symcom.com • 800-843-8848 • fax: 605-348-5685
36
Available Models:
Features:
Protects from low and high voltage, and
rapid cycle
DIN rail or surface mountable
LED Diagnostics
Adjustable restart delay setting
A
pprovals:
Specications
460-100-SP
460-200-SP
The Model 460-100-SP
is used on 95-120VAC, 50*/60Hz single-phase
motors and the 460-200-SP is used on 190-240VAC,
50*/60Hz single-phase motors to protect them
from damaging high and low voltage conditions.
An adjustment knob allows the user to set a 1-500
second restart delay. The variable restart delay
is also a power-up delay and can be utilized to
stagger-start motors on the same system.
A unique microcontroller-based, voltage-sensing
circuit constantly monitors the voltage to detect
harmful power line conditions. When a harmful
condition is detected, the MotorSaver’s output
relay is deactivated after a specified trip delay. The
output relay reactivates after power line conditions
return to an acceptable level and a specified
amount of time has elapsed (restart delay). The trip
delay prevents nuisance tripping due to rapidly
fluctuating power line conditions.
For more information see:
See Appendix A, page 69, Figure 11 for dimensional
drawing.
See Appendix B, page 77, Figure 33 for typical
wiring diagrams.
Model 460-xxx-SP
single-phase voltage monitor, din rail mount, adjustable restart delay
Single-Phase Voltage Monitor
Class of Protection ..............................IP20, NEMA 1 (finger safe)
Relative Humidity ..............................10-95%, non-condensing per IEC 68-2-3
Terminal Torque. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 in.-lbs.
Wire Type .....................................Stranded or solid 12-20 AWG, one per terminal
Standards Passed
Electrostatic Discharge (ESD) .......................IEC 61000-4-2, Level 3, 6kV contact, 8kV air
Radio Frequency Immunity,
Radiated .......................................150 MHz, 10V/m
Fast Transient Burst .............................IEC 61000-4-4, Level 3, 3.5 kV input
power & controls
Surge
IEC ...........................................IEC 61000-4-5, Level 3, 4kV line-to-line;
Level 4, 4kV line-to-ground
ANSI/IEEE ....................................C62.41 Surge and Ring Wave
Compliance to a level of 6kV line-to-line
Hi-potential Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Meets UL508 (2 x rated V +1000V for 1 min)
Safety Marks
UL ............................................UL508 (File #E68520)
CE ............................................IEC 60947-6-2
Enclosure ......................................Polycarbonate
Dimensions ....................................3.5” H X 2.084” W X 2.350” D
(88.9 x 52.93 x 59.69mm)
Weight ........................................0.9 lb. (14.4 oz., 408.23 g)
Mounting Method ..............................35mm DIN rail or Surfact Mount
(#6 or #8 screws)
*Note: 50 Hz will increase all delay timers by 20%
Input Characteristics
Line Voltage
460-100-SP .....................................95-120VAC
460-200-SP .....................................190-240VAC
Frequency .....................................50*/60Hz
Functional Characteristics
Low Voltage (% of setpoint)
Trip ...........................................90% ±1%
Reset ..........................................93% ±1%
High Voltage (% of setpoint)
Trip ...........................................110% ±1%
Reset ..........................................107% ±1%
Trip Delay Time
Low or High Voltage ............................4 seconds fixed
Restart Delay Time
After a Fault ...................................1-500 seconds adjustable
After a Complete Power Loss ........................1-500 seconds adjustable
Output Characteristics
Output Contact Rating (1 Form C)
Pilot Duty .....................................480VA @ 240VAC, B300
General Purpose ................................10A @ 240VAC
General Characteristics
Ambient Temperature Range
Operating ...............................................-40° to 70°C (-40° to 158°F)
Storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -40° to 80°C (-40° to 176°F)
Maximum Input Power ..........................6 W