Motor Saver 201-575-AU Fiche technique Page 55

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 88
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 54
www.symcom.com • 800-843-8848 • fax: 605-348-5685
53
Available Models:
Features:
Compact design
Finger-safe terminals
DIN rail or surface mountable
LED state indicator
2 input channels
A
pprovals:
ISS-102A-LC (Latching Controller)
ISS-102AA-DCS (Dual Channel Switch)
ISS-102ACI-MC (Multi-function Controller)
ISS-102C-M-LC (MSHA* evaluated)
ISS-102CCI-M-MC (MSHA* evaluated)
* Mine Safety and Health Administration
Specications
The ISS-102
SymCom’s Model ISS-102 two-channel,
intrinsically-safe switch is designed for multiple
uses including a pump-up/pump-down (latching)
controller or two-channel switch. Two LEDs
indicate the state of the intrinsically-safe inputs
and output relays and user-selectable options are
available including a variable resistance threshold
for float inputs.The ISS-102 enclosure is surface or
DIN rail mountable.
-LC Each input channel is active when the
corresponding switch is closed. When the lag input
(CH2) is activated, the output closes. Applying
latching logic, the output contact remains closed
until the lead (CH1) and the lag (CH2) inputs are
deactivated. Sensitivity is fixed at 100kOhms with
a debounce time delay of 2 seconds.
-DCS This dual-channel switch has a debounce delay feature of 0.5 seconds. Resistance probes
or switches can be used on its inputs. Two LEDs illuminate the output state of either form
A relay. Sensitivity is fixed at 100kOhms with a debounce time delay of 0.5 seconds.
-MC By selecting the proper functionality through the dip switches, you can define a pump-
up or pump-down, single or dual channel non-latching switch. The sensitivity adjustment
(4.7k-100kOhms) allows you to define the input impedance at which the output relays (one
form A & one form C) will change state, with a debounce time delay of 0.5 or 2 seconds.
For more information see:
See Appendix A, page 69, Figure 11 for dimensional drawing.
Model ISS-102
two-channel intrinsically safe switch, din rail mount, options include switch only (-DCS),
single latching output (-LC), or multi-function controller (-MC)
Intrinsically Safe Relay
Terminal Torque ................................3.5 to 4.5 in.-lbs. (max. 6 in.-lbs.)
Provides intrinsically-safe circuits
in the following locations: .......................Division 1 and 2
Class I, Groups A,B,C,D;
Class II, Groups E,F,G;
and Class III
Entity Parameters ..............................V
oc
= 16.8V Po=Voc*Isc
I
sc
= 1.2mA 4
L
a
= 100mH
C
a
= 0.39uF
Standards Passed
Electrostatic Discharge (ESD) ....................IEC 61000-4-2, Level 3, 6kV contact, 8kV air.
Radio Frequency Immunity (RFI) .................IEC 61000-4-3, Level 3, 10V/m
Fast Transients .................................IEC 61000-4-4, Level 3, 4kV input power
Safety Mark ...................................UL913 Sixth Edition (File #E233355)
(except Models ISS-102C-M-LC & ISS-102CCI-M-MC which have been evaluated by MSHA)
Dimensions ................................3.5” H x 2.084” W x 2.350” D
(88.9 x 52.93 x 59.69mm)
Weight ........................................0.7 lb. (11.2 oz., 317.51 g)
Mounting Method ..........................35mm DIN rail or Surfact Mount (#6 or #8 screws)
Input Characteristics
Supply Voltage ................................120VAC
Functional Characteristics
Debounce Time ................................0.5 or 2 seconds
Probe Sense Voltage ........................5vdc pulsed
Output Characteristics
Output Contact Rating
Pilot Duty .....................................180VA @120VAC, C150
General Purpose ...............................5A @120VAC
Relay Contact Life (Electrical) ...................100,000 cycles min. @ rated load
Relay Contact Life (Mechanical) .................10,000,000 cycles
Output Relay Type:
ISS-102A-LC .................................One Form A
ISS-102AA-DCS ..............................Two Form A
ISS-102ACI-MC ..............................One Form A & One isolated Form C
ISS-102C-M-LC ..............................One Form C
ISS-102CCI-M-MC ...........................Two Form C (one isolated)
General Characteristics
Temperature Range ............................-20° to 55°C (-4° to 131°F)
Maximum Input Power .........................2 W
Wire range ....................................12 to 20 AWG
CATALOG_SYMCOM_2014.indd 53 6/10/14 11:06 AM